Reliable measurement at all sites

Metrum EQC (Energy Quality Control) are specifically adapted to be able to perform highly reliable energy controls on all sites; the unit is easily connected in for instance fuse boxes for measurement of voltage and current.

Measurement data is reported directly in a complete report template that can be submitted in event of customer complaint. In addition to the power measurement check, complete reporting according to the applicable voltage standards is included.

https://metrum.se/content/uploads/2018/06/eqcpreview-e1530088579811.jpeg
Metrum EQC

Could it be easier?

The portable EQC-instrument is designed to be user friendly and sufficiently small to fit for instant measurement of energy and power quality.

The unit is also easy to manage, just specify start value and press "Start measurement". As simple as that.

Soon you will be able to download brochures and other documents here. For more information, do not hesitate to contact us!

Technical specifications

Measurement Inputs

Parameters Specification Information EQC
Voltage channels 0 - 275 V RMS Standard measurement (Class A) 3
Current channels 0.05 A - 240 A RMS with standard current clamp Specially calibrated current clamps 4

Supply

Parameters Specification Information EQC
Supply voltage 85-264 VAC or 110-375 VDC Supplied via measurement input
Power 5 W
Built-in backup Yes

Conformance

Parameters Specification Information EQC
IEC 61000-4-30 Class A Reference instrument Yes
IEC 61000-4-7 Harmonics Yes
IEC 61000-4-15 Flicker Yes
EN 50160 Compiled in the instrument Yes
EIFS 2013:1 Compiled in the instrument Yes
Norwegian injunction FoL Compiled in the instrument Yes
PQDIF format Export option Yes

Hardware

Parameters Specification Information EQC
Memory 128MB
Sampling rate 12,8 kHz
Accuracy < 0,1 %
Resolution Voltage/current channels 16 bits
Bandwidth 3,5 kHz
Input impedance Voltage channels >1 MΩ
Input impedance Current inputs For current clamps with voltage output >1 MΩ
Anti-alias filter Yes
PLL synchronization Yes

Communication

Parameters Information EQC
RS-232 Modem port Yes
RS-232 Computer port Yes

Physical data

Parameters Information
Size (W x L x D) 160 x 240 x 60 mm
Weight 1,3 kg
Working temperature -10 °C to +55 °C
Humidity 10 % - 85 %, non-condensing